We have compiled a list of products required to satisfy your brief, please copy and paste the text below into your specification:
The gas ventilation/gas interlock system to comply with AS/NZS 5601.12022 shall be manufactured by Oceania Gas Safety
The model to be supplied is the OGS Merlin 1200S System which is 140mm (height) x 190mm (length) x 62mm (depth). The Merlin 1200S can interlock with up to two fans by using air pressure differential switches. In the event where the ventilation fails the gas solenoid valve should be closed and the system will go into ‘fan fault’ alarm.
1 x OGS Merlin 1200s Panel
2 x Air PD Switch (20-300PA)
1 x Goldseal Gas Solenoid Valve (size)
1 x Emergency Stop Button (one per exit)
There should be a means of isolation by each main exit and any emergency knock-off buttons should be connected to the gas safety system.
Also connections can be made to the fire alarm and BMS to shut the gas solenoid valve in the event of a genuine alarm.
Contact All Controls for a quotation.
03 9123 1275