Merlin LPG Gas Detector

OGS is recognized within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have installed and commissioned natural gas,carbon monoxide & LPG sensors in applications such as boiler rooms, kitchens, car parks, aircraft hangers, factories and shopping centers.

The LPG sensor should be mounted in accordance with certain considerations. Do not position next to burners, heaters or ovens where temperatures above the room ambient may be experienced. It is, if possible, better to mount the sensors on the opposite wall. This is, of course, dependant on the size of the protected area. LPG is heavier than air and will therefore drop, meaning the Gas sensor should be mounted 30cm from the floor of the protected area. The LPG detectors at detection will go into alarm at 10% of the low explosion level. This will trigger isolation of the power supply to the solenoid and as such isolation of the gas supply. This can then be rectified by resolving the leak, allowing the sensor head to clear and resetting the attached Merlin panel.

OGS is recognized within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. Below are the models available for the XS range of detectors:

  • Natural Gas (Methane)
  • LPG
  • Carbon Monoxide

For any other gas monitors not listed above, please refer to the TFT range of OGS Gas detectors.

• Low level & high level alarm.
• Straightforward to install .
• Covered by Oceania Gas Safety 3 year warranty.

• Height – 95mm
• Width – 132mm
• Depth – 33mm

LPG Product Datasheet