Merlin LPG TFT Gas Detector

 Liquid Petroleum Gas

The TFT range of OGS detectors work in combination with the OGS Merlin range of Gas Detection panels and Utility Controllers. Semi conductor type sensor for industrial and commercial indoor applications. Compact, modern, digital design makes the units aesthetically pleasing and easy to install.

The LPG sensor should be mounted in accordance with certain considerations. Do not position next to burners, heaters or ovens where temperatures above the room ambient may be experienced. It is, if possible, better to mount the sensors on the opposite wall. This is, of course, dependant on the size of the protected area. LPG is heavier than air and will therefore drop, meaning the Gas sensor should be mounted 30mm from the floor of the protected area. The LPG detectors at detection will go into alarm at 10% of the low explosion level. This will trigger isolation of the power supply to the solenoid and as such isolation of the gas supply. This can then be rectified by resolving the leak, allowing the sensor head to clear and resetting the attached Merlin panel.

For further information on our Merlin gas detectors please refer to our product data sheet.

OGS is recognized within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. Below is our most popular gas detectors:

  • Natural Gas (Methane)
  • LPG
  • Carbon Monoxide
  • Oxygen
  • Refrigerants
  • Nitrogen Oxides

For any other gas monitors not listed above, please contact Oceania Gas Safety or your local representative for further information.

• Low level & high level alarm.
• Traffic light style gas level display indicator.
• Straightforward to install.
• Modbus RTU compatible
• Covered by Oceania Gas Safety 3 year warranty.

• Height – 140mm
• Width – 95mm
• Depth – 30mmh

OGS LPG Gas Detector TFT Datasheet (English)